Figure 15 DC Power Supply Terminal Block Positive and Negative Cable Lugs With Protective Sleeving
Step 4 For easier cable-management, insert the negative lead cable first. Replace the ground lug with cable in the following
order:
a. Flat Washer
b. Ground lug with negative wire
c. Kepnut screw
1
Negative lug and wire with sleeving wrapped around the
wire and end of lug
3
Location of sleeving wrapped around the wire and end of
the grounding stud
2
Positive lug and wire with sleeving wrapped around the
wire and end of lug
4
Earth ground lug and wire
This unit might have more than one power supply connection. All connections must be removed to de-energ
OFF
-48/-60V 40A
280024
1 2
4
3